CoolTherm
Manual / Bedienungsanleitung
3.2 | Electrical functions |
|
|
|
|
| function check valve / fan control. | yes | □ | no | □ |
| comments: |
|
|
|
|
| ......................................................................................................................................... | □ | |||
| fans shut down when rear door is opened | yes | □ | no | |
| comments: |
|
|
|
|
| ......................................................................................................................................... | □ | |||
| function check smoke detector | yes | □ | no | |
| comments: |
|
|
|
|
| ......................................................................................................................................... | □ | |||
| function check temperature control | yes | □ | no | |
| comments: |
|
|
|
|
| ......................................................................................................................................... | □ | |||
| function check automatic door opening | yes | □ | no | |
| adjustment magnet plates see manual “initial commissioning automatic door” |
|
| ||
| comments: |
|
|
|
|
| ......................................................................................................................................... | □ | |||
| function check water sensor | yes | □ | no | |
| comments: |
|
|
|
|
| ......................................................................................................................................... | □ | |||
| malfunction indicator function | yes | □ | no |
comments:
.........................................................................................................................................
3.3 | Thermal checks |
| □ |
| □ |
| condensate occurrence at heat exchanger | yes | no | ||
| comments: |
|
|
|
|
| ......................................................................................................................................... |
| |||
| chilled water feed at heat exchanger |
| ............... | °C |
|
| chilled water return at heat exchanger |
| ............... | °C |
|
| air temperature in the cabinet |
|
|
|
|
| at the heat exchanger inlet: |
| ............... | °C |
|
| air temperature in the cabinet |
|
|
|
|
| at the heat exchanger outlet: |
| □ | °C | □ |
| chilled water cycle bled: | yes | no |
CoolTherm | 01_998_330_0_k | page / Seite 38/83 |