CoolTherm

Manual / Bedienungsanleitung

During all work on and with the unit, observe:

The related applicable regulations (e. g. VDE regulations or other applicable national regulations)

The applicable accident prevention instructions (BGV)

The applicable rules

The applicable laws on the protection of the environment

Only operate the unit if it is in correct working condition. On the occurrence of malfunctions or faults, you must shut down the unit immediately and inform the responsible member of staff

in the operating organisation.

You are only allowed to use the unit again after its correct function has been re- established.

Caution hot surface

Faulty fans, power supplies, control circuit boards can run hot.

Prior to starting work, let these cool down.

2.Operating conditions

Correct use

The unit is a server cabinet cooling device and is only used for the removal of heat from server cabinets to protect temperature sensitive components. The cooling system in the cabinet is thermally independent of the room air. Total heat load of the installed equipment is

taken out of the room using the chilled water circuit. Note: Under special conditions a very small amount can dissipate to the room (approx. 05, kW)

For reliable function of the CoolTherm, chilled water

must be available in the correct amount, and at the correct temperature and pressure. Observe water quality as per VGB-R 455 P. (see Appendix)

Ambient temperature:

10°C / 50°F to 35°C / 95°F

 

(other temperatures upon request)

 

Temperatures on use of RMS with

 

temperature-dependent alarm:

 

20°C / 68°F to 25°C / 77°F

Absolute humidity in the installation location:

8 g H2O/ kg air maximum

Water temperature, feed:

12°C / 53°F

 

(other temperatures upon request)

Water temperature, return:

18°C / 64.4°F

 

(other temperatures upon request)

CoolTherm

01_998_330_0_k

page / Seite 5/83

Page 7
Image 7