CoolTherm

Manual / Bedienungsanleitung

CoolTherm 01_998_330_0_k page / Seite 25/83
5.6 Sealing of cabinet
The air tightness of the housing corresponds to RAL 652
To ensure the optimal cooling function the cabinet must be sealed:
- Pipe entries should be cut into the foam and properly closed with a extra foam if required.
- Cable entries should be closed with the pivoting plate and foamed material
- Air flows on the warm and cold sides of the cabinet must be separated from each other
5.7 Automatic door opening
Cover CoolTherm with automatic door opening

Function

Front and rear door are kept closed with two electromagnets.
The door will be pushed off smoothly by a gas pressure spring, if the power supply of the
electromagnets breaks.
The electric door opening can prevent damages through overtemperature in the rack as well as
occurring humidity.
If the doors are opened the thermal load can disappear to the room. There is no overheating of the
servers.
The suck in of air with water droplets can also be prevented (Door opening due to humidity alarm).
When the rear door is opened, the fans will be shut down.
gas pressure
springs
retaining plate
upper magnet
Upper cable
entry
(standard)