5.6Sealing of cabinet

The air tightness of the housing corresponds to RAL 652

To ensure the optimal cooling function the cabinet must be sealed:

-Pipe entries should be cut into the foam and properly closed with a extra foam if required.

-Cable entries should be closed with the pivoting plate and foamed material

-Air flows on the warm and cold sides of the cabinet must be separated from each other

5.7Automatic door opening

gas pressure

springs

Upper cable

entry

(standard)

upper magnet

retaining plate

Cover CoolTherm with automatic door opening

Function

Front and rear door are kept closed with two electromagnets.

The door will be pushed off smoothly by a gas pressure spring, if the power supply of the electromagnets breaks.

The electric door opening can prevent damages through overtemperature in the rack as well as occurring humidity.

If the doors are opened the thermal load can disappear to the room. There is no overheating of the servers.

The suck in of air with water droplets can also be prevented (Door opening due to humidity alarm).

When the rear door is opened, the fans will be shut down.

 

CoolTherm

01_998_330_0_k

page / Seite 25/83