Lightwave Communications 3200 user manual Appendix D -DC Power

Models: 3200

1 88
Download 88 pages 3.07 Kb
Page 79
Image 79
Appendix D -DC Power

Appendix D -DC Power

The DC power version of the ConsoleServer 800 must be installed in a restricted access location. Per the intent of the National Electrical Code, a restricted access location is an area intended for access by qualified or trained personnel only, with access controlled by some sort of locking mechanism, such as a key lock or access card system.

Installation:

Materials:

small flat-blade screwdriver

wire stripper

ConsoleServer 800 DC power connector kit

wires to 48 VDC power (see Appendix D for specifications)

1.Turn off the circuit breaker to the DC power supply.

2.Select a three-wire set (-48V, –48 Return, and Power Supply Ground) from the power supply.

3.Strip 0.35 inches (89 mm) of insulation from each wire.

4.Insert a small flat-blade screwdriver in the provided connector to depress the internal wire clamp.

5.Insert the appropriate wire into the connector. Remove the screwdriver. Check that the clamp has captured the wire. Repeat steps 4 and 5 for all wires.

6.Attach the provided strain relief to the connector. Be sure to use a tie-wrap to firmly attach the strain relief to the cable.

7.Attach the connector to the socket on the back of the ConsoleServer. Repeat the above steps to attach the redundant power input.

Power On/Off Switch Manual backgroundManual background o Feed Through Headers

Manual background Fan

48V Return

PSU Gnd

-48V DC

75

Page 79
Image 79
Lightwave Communications 3200 user manual Appendix D -DC Power