Lincoln Electric SVM208-A Troubleshooting And Repair, ROTOR “FLASHING” CIRCUIT TEST continued

Models: SVM208-A

1 101
Download 101 pages 8.56 Kb
Page 67
Image 67
F-19

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

F-19

TROUBLESHOOTING AND REPAIR

F-19

 

ROTOR “FLASHING” CIRCUIT TEST (continued)

Manual backgroundWARNING

MOVING PARTS can injure.

Keep away from moving parts.

-------------------------------------------------------------------

ENGINE EXHAUST can kill.

Use in open, well ventilated areas or vent exhaust to the outside.

-------------------------------------------------------------------

5.Start the engine and run it at High Idle (3700 - 3800 RPM).

6.The DC ammeter should read between 0.15 and 0.30 amps.

7.If the DC ammeter reads 0.0 amps, check for flashing voltage between lead #202 from the brush holder and case ground (lead #201). See Figure F.4, and the Wiring Diagram. Normal flashing voltage is 2.05 VDC.

8.If normal flashing voltage is present, perform the Rotor Resistance Test. Also be sure that all #201 leads have continuity (zero ohms) to case ground.

9.If flashing voltage is not measured, check from lead 205 on the diode bridge D3 to case ground. Normal readings are around 3 VAC. If no flashing voltage is present, the engine mag- neto may be faulty. Check lead 205 back to magneto and measure for voltage there.

10.If there is AC volts at the diode bridge, the diode may be open. Check diode and move leads over if need be.

BULLDOG® 140

Page 67
Image 67
Lincoln Electric SVM208-A Troubleshooting And Repair, ROTOR “FLASHING” CIRCUIT TEST continued, Return to Section TOC, F-19