Lochinvar 51-211 Requirements for installation in Canada, Sizing, Model, Max Vent/Air, Kit Number

Models: 51-211

1 80
Download 80 pages 15.82 Kb
Page 16
Image 16
Requirements for installation in Canada

3 General venting

Requirements for installation in Canada

1.Installations must be made with a vent pipe system certified to ULC-S636.

IPEX is an approved vent manufacturer in Canada supplying vent material listed to ULC-S636.

2.The first three (3) feet of plastic vent pipe from the appliance flue outlet must be readily accessible for visual inspection.

3.The components of the certified vent system must not be interchanged with other vent systems or unlisted pipe/fittings.

4.The 2" and 3" Concentric Vent Kits available from Lochinvar (see Section 4 – Sidewall Termination – Optional Concentric Vent) and the 2" and 3" Concentric Vent Kits available from IPEX are approved for use on the Knight wall mount boiler. Both kits are listed to the ULC-S636 standard for use in Canada.

Sizing

The Knight wall mount boiler uses model specific combustion air intake and vent piping sizes as detailed in Table 3A below.

Table 3A Maximum Combustion Air and Vent Piping Lengths

Model

2" Max Vent/Air

3" Max Vent/Air

51

 

40 feet

100 feet

81

 

40 feet

100 feet

106

 

40 feet

100 feet

151

 

N/A

100 feet

211

 

N/A

100 feet

 

 

Increasing or decreasing combustion air or

NOTICE

vent piping sizes is not authorized.

Installation & Operation Manual

Minimum / Maximum allowable combustion air and vent piping lengths are as follows:

Combustion Air = 12 equivalent feet minimum / 100 equivalent feet maximum

Vent = 12 equivalent feet minimum / 100 equivalent feet maximum

When determining equivalent combustion air and vent length, add 5 feet for each 90° elbow and 3 feet for each 45° elbow.

EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2) 45° elbows + (1) concentric vent kit (CVK3003) = 49 equivalent feet of piping.

NOTICE

The appliance output rating will reduce

by up to 1.5% for each 25 feet of vent

 

length.

Table 3B Concentric Vent Kit Equivalent Vent Lengths

Model

Kit Number

Equivalent Vent

 

 

Length

51 - 106

CVK3008

3 feet

 

 

 

51 - 211

CVK3003

3 feet

 

 

 

Sizing 16 Table 3A Maximum Combustion Air and Vent Piping Lengths