Lochinvar 51-211 Number of Units, Model, Required Pipe Sizes, Hydronic piping continued, Boiler

Models: 51-211

1 80
Download 80 pages 15.82 Kb
Page 41
Image 41
Model

Installation & Operation Manual

6 Hydronic piping (continued)

Figure 6-4Multiple Boilers - Single Temperature Zoned with Circulators

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

Number of Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

 

4

5

6

7

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Required Pipe Sizes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51

 

1"

 

1-1/4"

1-1/2"

2"

2"

2"

2"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

81

 

1-1/4"

1-1/2"

2"

2"

2-1/2"

2-1/2"

2-1/2"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ZONE #1

 

 

 

106

 

1-1/2"

2"

 

2"

2-1/2"

2-1/2"

2-1/2"

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

151

 

2"

 

2"

 

2-1/2"

2-1/2"

3"

3-1/2"

3-1/2"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

211

 

2"

 

2-1/2"

3"

3-1/2"

3-1/2"

4"

4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REDUCING VALVE

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ZO

NE

#2

 

ZO

NE

#3

 

ZO

NE

#4

 

 

 

 

 

BACKFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAUGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PREVENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAKE UP

FLOW CHECK

WATER

VALVE

SYSTEM SUPPLY

(TYPICAL)

SENSOR

 

AIR SEPARATOR

ZONE CIRCULATORS

 

(TYPICAL)

Number of UnitsRequired Pipe Sizes EXPANSION

TANK

BALL VALVE

MAY SUBSTITUTE LOW LOSS HEADER

 

(TYPICAL)

 

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

DRAIN POINT

 

 

 

(TYPICAL)

 

ANTI-SCALD

 

 

 

HOT

 

Y-STRAINER

MIXING VALVE

 

 

WATER

 

(RECOMMENDED)

OUT

 

(TYPICAL)

DOMESTIC

 

 

 

HOT WATER

 

BOILER

 

CIRCULATOR

COLD

 

 

CIRCULATOR

 

 

WATER

 

 

 

IN

PRESSURE

RELIEF VALVE

BOILER 2

BOILER 1

(MEMBER 1)
(LEADER)

 

TEMPERATURE /

 

 

INDIRECT

DRAIN

UNION

DHW TANK

PRESSURE

 

(TYPICAL)

 

GAUGE

 

 

 

 

 

NOTICE

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.

BOILER 2 41 (MEMBER 1)

Page 41
Image 41
Lochinvar 51-211 Number of Units, Model, Required Pipe Sizes, Hydronic piping continued, Installation & Operation Manual