Installation & Operation Manual

6 Hydronic piping (continued)

Figure 6-6Multiple Boilers - Multiple Temperatures

Number of Units

Model

2

3

4

5

6

7

8

Required Pipe Sizes

51 1" 1-1/4" 1-1/2" 2" 2" 2" 2"

811-1/4" 1-1/2" 2" 2" 2-1/2" 2-1/2" 2-1/2"

106 1-1/2" 2"

2" 2-1/2" 2-1/2" 2-1/2" 3"

1512" 2" 2-1/2" 2-1/2" 3" 3-1/2" 3-1/2"

211

2" 2-1/2" 3" 3-1/2" 3-1/2" 4"

4"

 

 

 

 

WIRES TO

 

 

 

 

LOOP

 

PRESSURE

TEMPERATURE

TEMPERATURE

SENSORS

 

TEMPERATURE

BACKFLOW

REDUCING VALVE

LOOP #1

LOOP #2

LOOP #3

PREVENTER

 

 

 

MIXING VALVES

 

PRESSURE

 

 

(TYPICAL)

 

GAUGE

 

 

 

MAKE

SYSTEM

 

 

 

UP

SUPPLY

 

 

 

WATER

SENSOR

 

 

 

AIR SEPARATOR

 

EXPANSION

 

 

24V

 

TANK

 

 

SIGNAL

 

 

 

 

TO MIXING

 

MAY SUBSTITUTE

 

 

VALVES

 

LOW LOSS HEADER

 

 

 

BALL VALVE

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

 

 

(TYPICAL)

 

120VAC TO PUMPS

 

 

DRAIN POINT

 

 

 

 

(TYPICAL)

BOILER

MULTI-TEMP

 

 

 

 

 

 

CIRCULATOR

LOOP CONTROL

 

 

 

 

(OPTIONAL)

 

 

 

 

 

SHIELDED CABLE TO

 

FLOW CHECK

DOMESTIC

BOILER CONTROL

 

 

HOT

 

VALVE

HOT WATER

ANTI-SCALD

WATER

 

 

CIRCULATOR

MIXING

OUT

Y-STRAINER

 

 

VALVE

COLD

(RECOMMENDED)

 

 

 

WATER

 

 

 

 

IN

 

BOILER

BOILER

 

 

 

TEMPERATURE /

 

UNION

PRESSURE

DRAIN

(TYPICAL)

GAUGE

INDIRECT

 

 

DHW TANK

IMG00188

CAUTION

NOTICE

Mixing valves are required for the protection of low temperature loops.

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.

43

Page 43
Image 43
Lochinvar 51-211 operation manual Required Pipe Sizes