Installation & Operation Manual
6 Hydronic piping
Figure 6-2 Pressure Drop vs. Flow - Models 51 - 211

 6
6 




Table 6A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
| 
 | 
 | 
 | 20°F Temperature Rise Applications | 
 | 
 | |||
| Model | GPM | FT/HD | Minimum Pipe | 
 | Pump | 
 | 
 | |
| Size | Grundfos | TACO | B & G | Armstrong | ||||
| 
 | 
 | 
 | ||||||
| 51 | 5.1 | 11 | 1" | 0011 | E7 | |||
| 81 | 7.5 | 24 | 1" | 0011 | E7 | |||
| 106 | 9.8 | 27 | 1" | 0013 | E11 | |||
| 151 | 14.0 | 20 | 1" | 0011 | E7 | |||
| 211 | 19.6 | 29 | 1" | E9 | ||||
| 
 | 
 | 
 | 25°F Temperature Rise Applications | 
 | 
 | |||
| Model | GPM | FT/HD | Minimum Pipe | 
 | Pump | 
 | 
 | |
| Size | Grundfos | TACO | B & G | Armstrong | ||||
| 
 | 
 | 
 | ||||||
| 51 | 4.1 | 7.3 | 1" | 0014 | E7 | |||
| 81 | 5.9 | 15.0 | 1" | 0014 | E7 | |||
| 106 | 7.7 | 17.5 | 1" | 0014 | E7 | |||
| 151 | 11.0 | 12.8 | 1" | 0014 | E7 | |||
| 211 | 15.5 | 19.0 | 1" | 0013 | E7 | |||
| 
 | 
 | 
 | 
 | 35°F Temperature Rise Applications | 
 | 
 | ||
| Model | GPM | 
 | FT/HD | Minimum Pipe | 
 | Pump | 
 | 
 | 
| 
 | Size | Grundfos | TACO | B & G | Armstrong | |||
| 
 | 
 | 
 | 
 | |||||
| 51 | 2.9 | 
 | 4.1 | 1" | 007 | |||
| 81 | 4.2 | 
 | 7.3 | 1" | 007 | |||
| 106 | 5.5 | 
 | 9.8 | 1" | 007 | |||
| 151 | 7.9 | 
 | 10 | 1" | 008/0010 | |||
| 211 | 11.0 | 
 | 10.1 | 1" | 0010 | |||
| 
 | Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude | |||||||
| NOTICE | ||||||||
| 
 | 
 | models. | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| NOTICE | Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude | |||||||
| 
 | 
 | models. | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| NOTICE | The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation. | |||||||