Lochinvar 51-211 Field wiring, Installation must comply with, Line voltage connections

Models: 51-211

1 80
Download 80 pages 15.82 Kb
Page 52
Image 52
8 Field wiring

Installation & Operation Manual

8 Field wiring

￿WARNING ELECTRICAL SHOCK HAZARD – For your safety, turn off electrical power supply

before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.

3.

Wire the boiler pump as shown in FIG. 8-2.

4.

When connecting a domestic hot water (DHW) pump,

 

connect the wiring to the line voltage terminal strip as

 

shown in FIG. 8-2.

5.

To activate a system pump, wire as shown in FIG. 8-2. If

NOTICE

￿CAUTION

Wiring must be N.E.C. Class 1.

If original wiring as supplied with boiler must be replaced, use only type 105°C wire or equivalent.

Boiler must be electrically grounded as required by National Electrical Code ANSI/NFPA 70 – latest edition.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

the motor is larger than 1/8 hp or 1.8 amps, you must isolate

with a relay.

Figure 8-2Line Voltage Field Wiring Connections

Figure 8-1Remove Bezel

Figure 8-2Line Voltage Field Wiring Connections REMOVE BEZEL

Installation must comply with:

1.National Electrical Code and any other national, state, provincial, or local codes, or regulations.

2.In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local codes.

Line voltage connections

1.Remove bezel as shown in FIG. 8-1.

2.Connect 120 vac power wiring to the line voltage terminal strip in the junction box, as shown in FIG. 8-2.

2.Provide and install a fused disconnect or service switch (15 amp recommended) as required by the code (see FIG. 8-2).

Figure 8-1Remove Bezel 52 Installation must comply with:

Low voltage connections

1.Route all low voltage wires through the knockouts in the bottom front right side, just under the control panel, as shown in FIG. 8-3.

2.Connect low voltage wiring to low voltage connection board as shown in FIG. 8-4 on page 55 of this manual and the boiler wiring diagram.

Figure 8-3Routing Field Wiring

LOW VOLTAGE

CONNECTION BOARD

LOW VOLTAGE

WIRING KNOCKOUTS

LINE VOLTAGE

JUNCTION BOX

LINE VOLTAGE

WIRING KNOCKOUTS

Page 52
Image 52
Lochinvar 51-211 Field wiring, Installation must comply with, Line voltage connections, Low voltage connections