Lochinvar 51-211 Sidewall direct venting continued, 2A Clearance to Gravity Air Inlets

Models: 51-211

1 80
Download 80 pages 15.82 Kb
Page 23
Image 23
4 Sidewall direct venting (continued)

Installation & Operation Manual

4 Sidewall direct venting (continued)

Vent/air termination – sidewall

Figure 4-1CAlternate Venting Arrangement (if Space Allows) w/Field Supplied Fittings

TO BOILER

INTAKE AIRCOUPLING

Figure 4-2AClearance to Gravity Air Inlets CONNECTION

12” MIN

15” MAX

FROM BOILER

VENT PIPE

CONNECTION

BIRD SCREEN

12”

MIN

BIRD

SCREEN

GRADE OR

SNOW LINE

ALTERNATE VENTING ARRANGEMENT

(IF SPACE PERMITS)

Figure 4-1DAlternate Venting Arrangement - Typical Stainless Steel Sidewall Termination of Air and Vent w/ Field Supplied Fittings

TO BOILER

 

INTAKE AIR

12" MIN

CONNECTION

15" MAX

FROM

 

BOILER

 

VENT PIPE

 

CONNECTION

 

12" MIN

BIRD SCREEN

GRADE OR SNOW LINE

5. Maintain clearances as shown in FIG.’s 4-1A thru 4-3B,

pages 22 - 23. Also maintain the following:

a.

Vent must terminate:

 

• At least 6 feet from adjacent walls.

 

• No closer than 12 inches below roof overhang.

 

• At least 7 feet above any public walkway.

 

• At least 3 feet above any forced air intake within

 

10 feet.

 

• No closer than 12 inches below or horizontally

 

from any door or window or any other gravity air

 

inlet.

b.

Air inlet must terminate at least 12 inches above

Figure 4-2AClearance to Gravity Air Inlets

12"

MIN.

VENT / AIR

Figure 4-3AClearance to Forced Air Inlets TERMINATION 12"

Manual backgroundMIN.

12"

Manual background MIN.

Figure 4-2BAlternate Clearance to Gravity Air Inlets w/ Field Supplied Fittings

12”

MIN

BIRD

SCREEN

(TYPICAL)

12”

MIN

12”

Manual background MIN

Figure 4-3AClearance to Forced Air Inlets

IF LESS

THAN 10’

VENT / AIR

36"

TERMINATION

MIN.

 

FORCED AIR

INLET

7' MIN. ABOVE ANY PUBLIC WALKWAY

Figure 4-3BAlternate Clearance to Forced Air Inlets w/ Field Supplied Fittings

grade or snow line; at least 12 inches below the vent

termination; and the vent pipe must not extend

more than 24 inches vertically outside the building

as shown in FIG. 4-1B. Condensate could freeze and

block vent pipe.

c. Do not terminate closer than 4 feet horizontally

from any electric meter, gas meter, regulator, relief

valve, or other equipment. Never terminate above or

below any of these within 4 feet horizontally.

6. Locate terminations so they are not likely to be damaged by

foreign objects, such as stones or balls, or subject to buildup

of leaves or sediment.

7’ MIN ABOVE ANY PUBLIC WALKWAY

IF LESS

THAN 10’

36”

MIN

FORCED AIR

INLET

BIRD

SCREEN

(TYPICAL)

Manual background 23 Manual background

Page 23
Image 23
Lochinvar 51-211 Sidewall direct venting continued, 2A Clearance to Gravity Air Inlets, 3A Clearance to Forced Air Inlets