Lochinvar 51-211 Check inlet gas supply, Natural Gas Pipe Capacity Chart, Gas connections

Models: 51-211

1 80
Download 80 pages 15.82 Kb
Page 50
Image 50
Table 7A Natural Gas Pipe Size Chart

Installation & Operation Manual

7 Gas connections

Table 7A Natural Gas Pipe Size Chart

Nominal

 

 

 

 

Natural Gas Pipe Capacity Chart

 

 

 

 

Iron Pipe

 

 

 

Length of Pipe in Straight Feet for 1/2 PSI

 

 

 

Size (Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

20

30

40

50

60

70

80

90

100

125

150

175

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

175

120

97

82

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

697

477

384

328

292

267

246

236

210

200

179

164

149

138

1-1/4

1400

974

789

677

595

543

502

472

441

410

369

333

308

287

1-1/2

2150

1500

1210

1020

923

830

769

707

666

636

564

513

472

441

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4100

2820

2260

1950

1720

1560

1440

1330

1250

1180

1100

974

871

820

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-1/2

6460

4460

3610

3100

2720

2460

2310

2100

2000

1900

1700

1540

1400

1300

3

11200

7900

6400

5400

4870

4410

4000

3800

3540

3330

3000

2720

2500

2340

4

23500

16100

13100

11100

10000

9000

8300

7690

7380

6870

6150

5640

5130

4720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

￿WARNING

Knight wall mount boilers are typically shipped ready to fire on natural gas. Check boiler rating plate to determine which fuel the boiler is set for. If set to natural gas, it may be converted to LP by installing an orifice (see page 13). In order to operate on LP gas, an orifice MUST BE installed. Failure to comply could result in severe personal injury, death, or substantial property damage.

Check inlet gas supply

NOTICE

CSA or UL listed flexible gas connections

are acceptable, but you must exercise

 

caution to ensure that the line has

 

adequate capacity to allow your boiler

 

to fire at full rate. Consult with local

 

codes for proper installation or service

 

procedures.

3.

Loosen the set screw one (1) full turn from inside the

 

pressure tap on top of the gas valve. Place the tubing of

 

the manometer over the tap once the set screw is

 

loosened as shown in FIG. 7-3.

4.

Slowly turn on the gas supply at the field installed

 

manual gas valve.

￿WARNING

DO NOT adjust gas valve outlet pressure. The gas valve is factory-set for the correct outlet pressure. This setting is suitable for natural gas and propane, requiring no field adjustment. Attempting to alter the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.

5.

Turn the power switch to the “ON” position.

6.

Adjust the temperature set point on the control panel of

 

the SMART SYSTEM control module to call for heat.

7.

Observe the gas supply pressure as the burner fires at

 

100% of rated input. Percent of burner input will be

 

displayed on the control panel.

8.

Ensure inlet pressure is within specified range.

 

Minimum and maximum gas supply pressures are

 

specified in this section of the manual.

The gas piping must be sized for the proper flow and length of pipe, to avoid excessive pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load.

If you experience a pressure drop greater than 1 inch w.c., the meter, regulator, or gas line is undersized or in need of service. Perform the steps below when checking inlet gas supply:

1.Turn the main power switch to the “OFF” position.

2.Shut off gas supply at the manual gas valve in the gas piping to the appliance.

Natural Gas Pipe Capacity Chart 50 Length of Pipe in Straight Feet for 1/2 PSI

9.

If gas supply pressure is within normal range and no

 

adjustments are needed, proceed on to Step 11.

10.

If the gas pressure is out of range, contact the gas utility,

 

gas supplier, qualified installer or service agency to

 

determine the necessary steps to provide proper gas

 

pressure to the control.

11.

Turn the power switch to the “OFF” position.

12.

Shut off the gas supply at the manual gas valve in the gas

 

piping to the appliance.

13.

Remove the manometer from the pressure tap on top of

 

the gas valve. Re-tighten the set screw inside the pressure

 

tap.

Page 50
Image 50
Lochinvar 51-211 Check inlet gas supply, Natural Gas Pipe Capacity Chart, Length of Pipe in Straight Feet for 1/2 PSI