4 Sidewall direct venting
Prepare wall penetrations
Installation & Operation Manual
Figure 4-4B Polypropylene Sidewall Termination Assembly
1.Use the factory supplied wall plate as a template to locate the vent and air intake holes and mounting holes.
Air pipe penetration:
a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.
Vent pipe penetration:
a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:
•3½ inch hole for 2 inch vent pipe
•4½ inch hole for 3 inch vent pipe
Drill 3/16" diameter holes for inserting the plastic anchors into the wall.
2. For Polypropylene Only: Install the vent and air intake |
sidewall adapters from Table 3F on page 20 into the vent |
plate. Slide the sidewall retaining bracket down the |
SIDEWALL ADAPTER (VENT)
GALVANIZED
THIMBLE
SIDEWALL
ADAPTER
(AIR)
WALL
PLATE
SIDEWALL
RETAINING
PLATE
VENT
PLATE
VENT
CAP
IMG00085
| sidewall adapters flush to the vent plate (FIG. |
3. | For PVC/CPVC Only: Install the vent and air intake |
| piping through the wall into the vent plate openings. |
| Use RTV silicone sealant to seal the air pipe. Use the |
| cement/primer listed in Table 3D on page 19 to seal the |
| vent pipe. |
4. | Mount and secure the vent plate to the wall, using stainless |
| steel screws. |
5. | Seal all gaps between the pipes and wall. Seal around the |
| plate to the wall assuring no air gaps. |
6. | Assemble the vent cap to the vent plate (see FIG.'s |
| and |
| cap screw hole openings and securely attach the vent cap |
| to the vent plate. |
7. | Seal all wall cavities. |
8. | PVC/CPVC terminations are designed to accommodate |
| any wall thickness of standard constructions per the |
| directions found in this manual. |
9. | Stainless steel terminations are designed to penetrate |
| walls with a thickness up to 9.25 inches of standard |
| construction. |
Figure 4-4A PVC/CPVC Sidewall Termination Assembly
VENT AIR
Prepare wall penetrations (Alternate - Field Supplied Option)
1.Air pipe penetration:
a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.
2.Vent pipe penetration:
a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:
•3½ inch hole for 2 inch vent pipe
•4½ inch hole for 3 inch vent pipe
b.Insert a galvanized metal thimble in the vent pipe hole as shown in FIG.
3.Use a sidewall termination plate as a template for correct location of hole centers.
4.Follow all local codes for isolation of vent pipe when passing through floors or walls.
5.Seal exterior openings thoroughly with exterior caulk.
Figure
ELBOW
AIR PIPING
VENT PIPING
BIRD SCREEN
AIR PIPING
VENT PIPING
WALL PLATE
GALVANIZED
THIMBLE
24
CENTERLINE WIDTH
VENT PLATE
VENT CAP
GALVANIZED |
| ELBOW |
THIMBLE |
| |
|
| |
| SIDEWALL | BIRD SCREEN |
|
| |
| TERMINATION PLATE |
|