3 General venting

Optional room air

NOTICE

Optional room air is intended for

commercial applications. Combustion air

 

 

piping to the outside is recommended for

 

residential applications.

Commercial applications utilizing the Knight wall mount boiler may be installed with a single pipe carrying the flue products to the outside while using combustion air from the equipment room. In order to use the room air venting option the following conditions and considerations must be followed.

The unit MUST be installed with the appropriate

 

room air kit (Table 3C).

The equipment room MUST be provided with

 

properly sized openings to assure adequate

Installation & Operation Manual

Air contamination

Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the boiler, they can form strong acids. The acid can eat through the boiler wall, causing serious damage and presenting a possible threat of flue gas spillage or boiler water leakage into the building.

Please read the information given in Table 1A, page 10, listing contaminants and areas likely to contain them. If contaminating chemicals will be present near the location of the boiler combustion air inlet, have your installer pipe the boiler combustion air and vent to another location, per this manual.

 

combustion air. Please refer to instructions provided

 

with the room air kit.

There will be a noticeable increase in the noise level

 

during normal operation from the inlet air opening.

Using the room air kit makes the unit vulnerable to

 

combustion air contamination from within the

 

building.

Please review Section 1, Prevent

 

Combustion Air Contamination, to ensure proper

 

installation.

 

Vent system and terminations must comply with the

 

standard venting instructions set forth in this

 

manual.

 

￿WARNING

￿WARNING

If the boiler combustion air inlet is located in a laundry room or pool facility, for example, these areas will always contain hazardous contaminants.

To prevent the potential of severe personal injury or death, check for areas and products listed in Table 1A, page 10 before installing the boiler or air inlet piping.

If contaminants are found, you MUST:

• Remove contaminants permanently.

—OR—

￿WARNING

When utilizing the single pipe method, provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.

• Relocate air inlet and vent

terminations to other areas.

Table 3C Optional Room Air Kit

Model

Kit Number

51 - 106

KIT30051

151 - 211

KIT30052

18

Page 18
Image 18
Lochinvar 51-211 operation manual Optional room air, Air contamination, Model Kit Number