Lochinvar 51-211 Minimum Temperature Rise, Pump, Variable speed pump option, UP26-96 FC/VS, Model

Models: 51-211

1 80
Download 80 pages 15.82 Kb
Page 39
Image 39
Variable speed pump option

Installation & Operation Manual

6 Hydronic piping (continued)

Variable speed pump option

Table 6B Recommended Variable Speed Pumps

Minimum Temperature Rise*

Model

 

Pump

 

Grundfos

TACO

Wilo

 

UP26-96 FC/VS

0013 IFC VS
Stratos 1.25 3 x 30

51/81

20.3

20.3

21.7

106

22.3

21.0

21.5

151

21.2

19.8

19.1

211

26.8

25.1

23.6

*The minimum temperature rise is derived from the chart in FIG. 6-2 with the firing rate and pump speed at 100% as shown in the table above.

The shaded regions of pump coverage are only available for applications with 230V (60 Hz) supply voltage, all others are to be 115V. (A field supplied relay is required to connect the 230V pump listed in the shaded area in Table 6B to the boiler high voltage terminal strip.)

Variable speed pump setup

Before operation, ensure the following:

-Pump is set for an input signal of 0 - 10Vdc by the dip switches on the pump control

-Pump is set for external signal control (if applicable)

-Pump is set for linear output (if applicable)

-If pump does not come equipped with a 0 - 10 Vdc input option, an optional module will be required from the vendor

NOTICE

Pump sizing and flow requirements are based on 20 feet of piping, 4 - 90° elbows, and 2 - fully ported ball valves.

NOTICE

It is required that near boiler piping systems utilize Primary/Secondary configurations as shown in FIG.’s 6-3 through 6-10 only. The use of other near boiler piping configurations could result in improper building and system flow rates leading to inadvertent boiler high limit shutdowns and poor system performance.

SMART SYSTEM / Multi-temperature loop control option

The Knight wall mount boiler is capable of producing up to three (3) set point temperatures to meet different space heating demands. When using more than one temperature demand it is necessary to protect the lower temperature loop from overheating. To help aid with this protection, Lochinvar offers the Multi- Temperature Loop Control Board Kit (RLY30086).

Table 6B Recommended Variable Speed Pumps 39 Minimum Temperature Rise*

Page 39
Image 39
Lochinvar 51-211 Minimum Temperature Rise, Variable speed pump option, B Recommended Variable Speed Pumps, Ifc Vs