12 Maintenance (continued)

Table 12B Heat Exchanger Cleaning Kits

Model

Kit

Part

Component

Number

Number

Description

 

 

 

CTN20005

Rear Refractory Cover

51 - 106

KIT30062

MSC20083*

Nylon 4" Wheel Brush*

 

 

MSC20085

1/4" x 12" Drill Extension

 

 

CTN20005

Rear Refractory Cover

151 - 211

KIT30063

MSC20083*

Nylon 4" Wheel Brush*

MSC20084

3mm Allen Wrench

 

 

 

 

MSC20086

1/4" x 24" Drill Extension

￿CAUTION * Do NOT use a metal brush. Only use the kit provided brush or an equivalent

replacement nylon brush.

Figure 12-3Rope Gasket - Heat Exchanger Door

ROPE GASKET

CAUTION: IF GASKET IS DAMAGED

DO NOT REUSE, THE HEAT EXCHANGER DOOR

MUST BE REPLACED.

Rope gasket is intended for sealing NOTICE combustion (FIG. 12-3). If damaged DO

NOT reuse, the heat exchanger door must be replaced. Consult factory for replacement heat exchanger door (kit WTR30002).

Installation & Operation Manual

Oiled bearing circulators

1.The circulator shipped with the Knight wall mount boiler is water-lubricated. No oiling is required.

2.Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s instructions. Over-oiling will damage the circulator.

3.Replace the boiler front access cover.