Section 2 | Installation Instructions |
|
|
Refrigeration System Installation
Remote Condensing Unit Only
QuietQube® | Remote | Line Set* | |
Ice Machine | Condensing Unit | ||
| |||
|
|
| |
RF1200C | RCU1075C | ||
RF2300C | RCU2375C | ||
|
| ||
|
|
|
*Line Set | Suction Line | Liquid Line | |
|
|
| |
RC 21/31/51 | 5/8 inch | 3/8 inch | |
(15.9 mm) | (9.5 mm) | ||
| |||
|
|
|
Important
Manitowoc remote systems are only approved and warranted as a complete new package. Warranty on the refrigeration system will be void if a new ice machine head section is connected to
USAGE WITH NON-MANITOWOC
CONDENSING UNITS
Manitowoc Remote Condensing Units are specifically designed for usage with a QuietQube® Ice Machine Head Section. Standard condensing units and Non- Manitowoc condensing units are not approved for use with a QuietQube® Ice Machine Head Section.
!Caution
The
Factory Equipment Refrigeration Amounts
ICE MACHINE HEAD SECTION
Each ice machine condensing unit ships from the factory with a
!Warning
Potential Personal Injury Situation
The QuietQube Condensing Unit contains the refrigerant charge. Installation and brazing of the line sets must be performed by a properly trained and EPA certified refrigeration technician aware of the dangers of dealing with refrigerant charged equipment.
!Caution
Never add more than nameplate charge to the refrigeration system for any application.
REFRIGERATION LINE SETS/TRAP KIT
Refrigeration Rated Tubing and Trap Kits are shipped capped with atmospheric pressure.
!Warning
Installation of a QuietQube® Condensing Unit may require the use of special equipment for placement. Trained and qualified personnel are required for proper rigging and lifting.
Part Number 000007644 3/11 | 10 |