IMPORTANT

Manifold gauges must be removed properly to ensure that no refrigerant contamination or loss occurs. A quick disconnect is required for the high side connection.

Recovery/Evacuation

1.Place the toggle switch in the OFF position.

2.Install manifold gauges, charging scale, and recovery unit or two-stage vacuum pump.

3.Open the high and low side valves on manifold gauges.

4.Perform recovery or evacuation:

A.Recovery: Operate the recovery unit as directed by the manufacturer’s instructions.

B.Perform a nitrogen pressure test to verify leaks are not present.

C.Evacuation prior to recharging: Pull the system down to 500 microns.

NOTE: Check access fittings for leaks with an electronic leak detector after charging the ice machine.