Refrigerant Recovery/Evacuation/Charging

Do not purge refrigerant to the atmosphere. Capture refrigerant using recovery equipment. Follow the manufacturer’s recommendations.

Install and uninstall your manifold gauge set correctly to prevent refrigerant loss.

IMPORTANT

Manitowoc Ice, Inc. assumes no responsibility for the use of contaminated refrigerant. Damage resulting from the use of contaminated refrigerant is the sole responsibility of the servicing company.

IMPORTANT

Replace the liquid line drier before evacuating and recharging. Use only a Manitowoc (O.E.M.) liquid line filter drier to prevent voiding the warranty.

Connections

Suction side of the compressor through the suction access fitting.

Discharge side of the compressor through the discharge access fitting.

IMPORTANT

Purge system with nitrogen while brazing to prevent build up of copper oxide in the refrigeration system.