9.Charge the system with the proper refrigerant to the nameplate charge.

10.Operate the ice machine for one hour. Then, check the pressure drop across the suction line filter-drier.

a)If the pressure drop is less than 2 psig, the filter-drier should be adequate for complete cleanup.

b)If the pressure drop exceeds 2 psig, change the suction line filter-drier and the liquid line drier. Repeat until the pressure drop is acceptable.

11.Operate the ice machine for 48-72 hours. Replace the suction line and liquid line drier if necessary.

12.Follow normal evacuation procedures.