.A complete Parts List is available at www.MillerWelds.com
4-12. Electrical Service Guide
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda- tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
Input Voltage | 200 | 230 | 460 | 575 | |
|
|
|
|
| |
Input Amperes At Rated Output | 48 | 42 | 21 | 17 | |
|
|
|
|
| |
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes |
|
|
|
| |
Circuit Breaker 1, | 60 | 50 | 25 | 20 | |
Normal Operating 3 | 70 | 60 | 30 | 25 | |
Min Input Conductor Size In AWG4 | 8 | 8 | 12 | 14 | |
Max Recommended Input Conductor Length In Feet (Meters) | 96 | 127 | 206 | 209 | |
(29) | (39) | (63) | (64) | ||
| |||||
|
|
|
|
| |
Min Grounding Conductor Size In AWG4 | 8 | 10 | 12 | 14 | |
Reference: 2005 National Electrical Code (NEC) (including article 630) |
|
|
|
|
1Choose a circuit breaker with
2
3“Normal Operating” (general purpose − no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.