COOLING OPERATION

COOL operation

Four-way valve/OFF

NO

Initial

w 8

COOLING

YES

 

Vane initial

 

setting

NO

 

Vane

 

55 deg downward angle

 

 

70 deg downward angle

 

NO

YES

 

Fan speed

 

 

 

 

LOW

 

NO

YES

 

Downward discharge

 

 

 

 

1 hour

 

 

YES

Vane setting notch

Vane horizontal

airflow

 

w9

Compressor YES thermostat ON

NO

Allowance cancel

NO

YES

3-minute

 

 

 

 

 

 

 

 

time delay

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

YES

6-minute

 

 

 

Allowance

YES

 

 

 

time delay

 

 

 

period

 

 

 

 

NO

 

 

 

NO

 

 

 

 

 

 

 

6 minute

 

 

 

NO

3-minute

 

 

 

 

 

 

 

 

 

time delay

 

 

 

 

compressor operation

 

 

 

 

 

 

 

 

YES

 

 

 

Allowance set

 

Coil frost protection

 

 

 

 

 

 

 

 

 

 

w 10

YES

 

 

 

 

 

 

 

Coil frost

 

 

 

 

 

 

 

protection

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

w 11

 

NO

 

 

 

 

 

 

 

Cooling area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

NO

10-minute

 

Indoor coil

NO

NO

 

 

 

 

compressor operation

 

1 min continue

 

 

 

YES

 

temperature is 50˚F

 

 

 

 

 

 

or higher

 

 

YES

 

 

 

Allowance cancel

 

YES

 

 

 

 

 

 

 

 

FAN speed

 

 

 

 

 

 

 

 

 

 

 

Coil frost

YES

Defrosting

NO

 

LOW

 

 

 

 

 

 

 

 

protection detection

 

 

 

 

 

 

prevention

 

temperature 30˚F

 

 

FAN speed

YES

 

 

NO

 

or lower

 

 

 

 

 

YES

 

 

LOW 5 min elapse

 

 

 

16-minute

 

 

 

 

 

NO

 

 

 

NO

 

 

 

 

 

 

 

 

 

compressor operation

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

6-minute

3-minute

 

 

 

YES

 

 

trouble

 

 

 

time delay

time delay

 

 

 

Indoor pipe

YES

 

 

 

 

 

 

 

 

 

 

 

temperature is 34˚F

 

 

 

 

 

 

 

 

or lower

 

 

 

 

 

 

 

 

NO

Coil frost

Coil frost

 

 

 

 

 

 

 

prevention

prevention release

 

 

 

 

Compressor ON

Compressor OFF

1

w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation changes during auto vane SWING, the auto vane will continue to swing.

w9 When operating TEST RUN, the thermostat will be continuously ON.

w10 After 3 minute compressor operation, if the indoor coil thermistor reads 5°F or below for 3 minutes, the compressor will stop for 6 minutes.

w11Heating area : Indoor coil temperature is more than 9 degrees above the room temperature. Cooling area : Indoor coil temperature is more than 9 degrees below the room temperature. FAN area : Indoor coil temperature is within 9 degrees either way of the room temperature.

21

Page 21
Image 21
Mitsubishi Electronics PKH24FL, PKH36FL, PKH30FL, PKH18FL service manual Cooling Operation