DRY OPERATION

DRY

operation

Four-way valve / OFF

NO

Initial dry

 

 

operation

 

 

YES

w8

Vane

Vane initial setting

setting notch

 

YES

Room temperature is

w12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

64°F or lower

 

 

 

 

 

 

NO

 

 

 

 

 

 

During

 

NO

 

 

 

 

compressor ON

 

 

 

 

 

 

YES

 

 

 

 

 

 

3-minute

 

NO

 

3-minute

YES

 

compressor

 

 

 

time delay

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

NO

 

NO

Compressor &

w9

 

YES

Compressor &

w9

 

 

 

 

thermostat ON

 

 

 

thermostat

 

 

 

 

 

 

ON

 

 

YES

 

 

 

NO

 

 

Compressor ON

 

NO

 

10-minute

NO

 

 

 

 

compressor

 

 

time completes

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

YES

 

 

 

YES

w13

 

 

 

 

 

 

 

10-minute compressor

 

 

Compressor ON

 

 

OFF timer start

 

 

 

time set

 

 

Compressor OFF

 

 

Compressor ON

 

 

 

w14

 

 

 

w14

 

Fan STOP

 

 

 

Fan speed LOW

 

 

1

 

 

 

 

 

w8—9 Refer to page OC276-21.

w12 When room temperature is 64°F or below, the compressor cannot operate.

When room temperature rises over 64°F the compressor starts after a 3-minute time delay. w13 Compressor ON time is decided by room temperature. Refer to page OC276-30.

w14 In dry operation, compressor ON makes the fan speed LOW. Also, when the compressor OFF and the pipe temperature is 79°F or less, the fan stops, or when the compressor OFF and the pipe temperature is below 43°F the fan speed changes to LOW mode.

It is not possible to set the fan speed with the remote controller

22

Page 22
Image 22
Mitsubishi Electronics PKH30FL, PKH36FL, PKH24FL, PKH18FL service manual DRY Operation, Yes