3

SPECIFICATIONS

 

 

 

MODELS : PKH18FL, PKH24FL, PKH30FL, PKH36FL

 

 

Item

 

 

Model

PKH18FL

PKH24FL

PKH30FL

PKH36FL

 

 

 

 

Cooling

*1

Btu/h

18,000

24,000

30,000

34,200

Capacity

Heating

*1

Btu/h

18,600[24,100/25,100]

25,000[30,500/31,500]

33,000[39,100/40,500]

38,000[44,100/45,500]

 

Heating

*2

Btu/h

10,700[16,200/17,200]

14,700[20,200/21,200]

19,000[25,100/26,500]

19,600[25,700/27,100]

Moisture removal

 

Pints/h

5.3

7.0

9.1

10.5

Power

Cooling

*1

kW

1.79

2.36

3.12

3.44

Consumption

Heating

*1

kW

1.56[3.16/3.46]

2.37[3.97/4.27]

3.02[4.82/5.22]

3.54[5.34/5.74]

 

Heating

*2

kW

1.34[2.94/3.24]

1.92[3.52/3.82]

2.48[4.28/4.68]

2.65[4.45/4.85]

EER

 

*1

 

10.1

10.2

9.6

9.9

SEER

 

 

 

11.1

10.2

10.6

10.5

HSPF

 

 

 

7.2

6.8

7.1

6.9

COP

 

*1

 

3.5

3.1

3.2

3.1

 

 

*2

 

2.3

2.2

2.2

2.2

INDOOR UNIT MODELS

 

 

PKH18FL

PKH24FL

PKH30FL

PKH36FL

External finish

 

 

 

 

 

 

 

 

Munsell 3.4Y 7.7/0.8

 

Power supply

 

 

V,phase,Hz

 

 

208/230,1,60

 

 

 

Max.fuse size (time delay)

A

 

 

15

 

 

 

 

Min.ampacity

 

 

 

A

 

 

12

 

 

13

 

 

 

 

 

 

 

 

 

Fan motor

 

 

 

F.L.A.

 

 

0.5

 

 

0.6

 

Booster heater

 

 

 

A(kW)

 

7.6/8.4[1.6/1.9]

 

 

8.7/9.6[1.8/2.2]

Airflow Hi-Lo

 

Dry

CFM

 

 

710-530

 

 

990-780

 

 

 

 

Wet

CFM

 

 

640-480

 

 

890-700

 

Sound level Hi-Lo

 

 

dB

 

 

FK1:48 -41

 

 

 

 

 

 

 

 

 

 

FK1:49-44

 

 

FK1:50-46

Unit drain pipe O.D.

 

 

in.

 

 

 

 

1-1/16 (or 7/8)

 

 

 

 

W

in.

 

 

55-1/8

 

 

66-5/32

 

Dimensions

 

D

in.

 

 

9-1/4

 

 

 

 

 

 

 

H

in.

 

 

13-3/8

 

 

 

 

Weight

 

 

 

lb

57

 

 

 

57

 

 

66

 

 

66

OUTDOOR UNIT MODELS

 

PUH18EK

 

 

 

PUH24EK1

 

 

PUH30EK1

 

 

PUH36EK1

External finish

 

 

 

 

 

 

 

 

Munsell 5Y 7/1

 

Power supply

 

 

V,phase,Hz

 

 

208/230,1,60

 

 

 

Max.fuse size (time delay)

A

20

 

 

 

 

 

 

30

 

 

30

 

 

 

20

 

 

 

 

Min.ampacity

 

 

 

A

16

 

 

 

16

 

 

20

 

 

22

Fan motor

 

 

 

F.L.A.

0.75

 

 

 

0.65+0.65

 

 

0.75+0.75

 

 

0.75+0.75

 

 

 

Model (type)

 

RH247NAB

 

 

 

NH33NBD

 

 

NH41NAD

 

 

NH47NAD

Compressor

 

 

 

R.L.A.

12

 

 

 

11.5

 

 

14.0

 

 

17.5

 

 

 

 

 

L.R.A.

37

 

 

 

54

 

 

73

 

 

87

Crankcase heater

 

 

A(W)

0.11/0.12[23/28]

 

 

0.16/0.17[33/39]

 

 

0.16/0.17[33/39]

 

 

0.16/0.17[33/39]

Refrigerant control

 

 

 

 

 

 

 

Capillary tube

 

Defrost method

 

 

 

 

 

 

 

 

Reverse cycle

 

Sound level

 

 

 

dB

53

 

 

 

55

 

 

55

 

 

55

 

 

 

 

 

 

 

 

 

 

W

in.

 

 

34-1/4

 

 

38-3/16

 

 

38-3/16

Dimensions

 

D

in.

 

 

11-5/8

 

 

13-9/16

 

 

13-9/16

 

 

 

H

in.

33-1/2

 

 

 

49-9/16

 

 

49-9/16

 

 

49-9/16

Weight

 

 

 

lb

131

 

 

 

202

 

 

245

 

 

246

REMOTE CONTROLLER

 

 

 

 

 

With indoor unit

 

Control voltage (by built-in transformer)

 

 

Indoor unit-remote controller:DC12V. Indoor unit-outdoor unit:DC12V

 

 

 

 

Name

 

 

 

 

 

R22

 

 

 

 

REFRIGERANT

 

Charge

 

5 lbs 8 oz

 

 

 

9 lbs 15 oz

 

 

10 lbs 2 oz

 

10 lbs 9 oz

 

 

 

Oil <Model>

L

0.52 <MS-56>

 

 

 

1.2 <MS32N-1>

 

 

1.3 <MS32N-1>

REFRIGERANT PIPING

 

 

 

 

 

Not supplied(optional parts)

 

 

 

 

Pipe size

 

Liquid

in.

 

 

3/8

 

 

1/2

 

 

1/2

 

 

 

 

 

 

 

 

Gas

in.

 

 

5/8

 

 

3/4

 

 

3/4

 

 

 

 

 

 

 

 

 

Connection

 

Indoors

 

 

 

 

 

Flared

 

 

 

 

method

 

Outdoors

 

 

 

 

 

Flared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Between the indoor

Height difference ft

130

 

 

 

164

 

 

 

164

& outdoor units

 

Piping length

ft

130

 

 

 

164

 

 

 

164

NOTES : *1.Rating conditions (cooling)-indoor : 80˚FDB,67˚FWB outdoor : 95˚FDB,75˚FWB.

 

 

 

 

 

 

 

(heating)-indoor : 70˚FDB,60˚FWB outdoor : 47˚FDB,43˚FWB.

 

 

 

 

*2.Rating conditions (heating)-indoor : 70˚FDB,60˚FWB outdoor : 17˚FDB,15˚FWB.

 

 

 

 

*3.Heating capacity and power consumption in [ ] includes heater operation at 208/230V.

 

 

 

 

Operating range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor intake air temperature

 

Outdoor intake air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

Maximum

 

95˚FDB,71˚FWB

 

 

 

115˚FDB

 

 

 

 

 

 

 

Minimum

 

67˚FDB,57˚FWB

 

 

 

0˚FDB *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

Maximum

 

80˚FDB,67˚FWB

 

 

 

75˚FDB,65˚FWB

 

 

 

 

 

 

 

Minimum

 

70˚FDB,60˚FWB

 

 

 

17˚FDB,15˚FWB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In case of the wind baffle is installed.

* (In case of the wind baffle is not installed, the minimum temperature will be 23˚FDB.)