3. WRONG WIRING ON SITE

3. WRONG WIRING ON SITE

3-1 Between remote controller and indoor unit

If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard.

3-2 Phenomenon due to wrong wiring between indoor and outdoor units

Wrong wiring

 

Mode

Thermostat

Phenomenon

 

 

 

 

 

 

 

 

OFF

Operation stops.

Indoor

Outdoor

COOL

 

 

ON

4-Way valve turns ON. 9 minutes later, check code “P8” appears

1

1

 

 

on remote controller display.

2

2

 

 

 

OFF

Cooling operation. Several minutes later, check code “P8” appears

3

3

 

 

on remote controller display.

HEAT

 

 

 

ON

Normal operation until first thermostat OFF.

 

 

 

 

 

 

 

 

 

 

 

OFF

Outdoor unit stops.

Indoor

Outdoor

COOL

 

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

1

1

 

 

remote controller display.

2

2

 

 

 

OFF

Operation stops.

3

3

 

HEAT

 

 

 

 

 

 

 

 

ON

Operation stops. 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

OFF

Outdoor unit stops.

Indoor

Outdoor

COOL

 

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

1

1

 

 

remote controller display.

2

2

 

 

 

 

 

 

OFF

Operation stops.

3

3

 

HEAT

 

 

 

 

 

 

 

 

ON

Operation stops. 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

OFF

Outdoor unit stops.

Indoor

Outdoor

COOL

 

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

1

1

 

 

remote controller display.

2

2

 

 

 

OFF

Operation stops.

3

3

 

HEAT

 

 

 

 

 

 

 

 

ON

Operation stops, 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Outdoor unit stops.

Indoor

Outdoor

COOL

 

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

1

1

 

 

remote controller display.

2

2

 

 

 

 

 

 

OFF

Operation stops.

3

3

 

HEAT

 

 

 

 

 

 

 

 

ON

Operation stops. 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

Disconnection between 1 and 1 or 2

 

OFF

Operation stops.

COOL

 

 

and 2.

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

OFF

Operation stops. 4-way valve turns OFF.

 

 

HEAT

 

 

 

 

ON

27 minutes later, check code “P8” appears on remote controller

 

 

 

 

 

 

display.

 

 

 

 

 

 

 

 

 

Disconnection between 3 and 3.

COOL

Normal operation.

 

 

 

 

 

 

 

 

 

 

 

OFF

Operation stops. 4-way valve turns OFF.

 

 

HEAT

 

 

 

 

ON

Operation stops. 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

 

 

43