DCA-100SSJU — PRE-SETUP

Table of Contents

DCA-100SSJUPRE-SETUP

General Inspection Prior to Operation

The DCA-100SSJU generator has been thoroughly inspected and accepted prior to shipment from the factory. However, be sure to check for damaged parts or components, or loose nuts and bolts, which could have occurred in transit.

Extension Cable

When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the Cable Selection Guide (Table 11 ) as a guide for selecting proper cable size.

Circuit Breakers

To protect the generator from an overload, a 3-pole, 250 amp, main circuit breaker is provided to protect the UNV output terminals from overload. In addition two single-pole, 20 amp GFCI circuit breakers are provided to protect the GFCI receptacles from overload.Three 50 amp load circuit breakers have also been provided to protect the load side of the generator from overload. Make sure to switch ALL circuit breakers to the "OFF" position prior to starting the engine.

NOTE

ALWAYS consult with a licensed electrician for correct extension cord wire size.

Table 11. Cable Selection (60 Hz, Single Phase Operation)

Current in

Load In Watts

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

At 120

At 240

 

 

 

 

 

 

 

 

Amperes

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

5

600

1200

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

7.5

900

1800

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

10

1200

2400

250

ft.

 

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

 

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 