18.Place the main, GFCI, and aux. circuit breakers in the ON position (Figure 53).
Figure 48. Voltage Adjust Control Knob
14.The ammeter (Figure 49) will indicate zero amps with no load applied.When a load is applied, the ammeter will indicate the amount of current that the load is drawing from the generator.
Figure 49. Ammeter
(No Load)
15.The engine oil pressure gauge (Figure 50) will indicate the oil pressure of the engine. Under normal operating conditions the oil pressure is approximately 35 to 65 psi. (241~448 kPa). When starting the generator
Figure 50. Oil
Pressure Gauge
16.The coolant temperature gauge (Figure 51) will indicate the coolant temperature. Under normal operating conditions the coolant temperature should be between 180~230°F (82~110 °C) Green Zone.
Figure 51. Coolant
Temperature Gauge
17.Thetachometergauge(Figure52) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.
Figure 52. Engine
Tachometer Gauge
Figure 53. Main, Aux. and GFCI
Circuit Breakers (ON)
19. Observe the generator's ammeter (Figure 54) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if a load is in use.
20.The generator will run until manually stopped or an abnormal condition occurs.
Starting (Auto Mode)
DANGER - ELECTRICAL SYSTEM HAZARDS
Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.
CAUTION - BACKUP GENERATOR USE
When connecting the generator to a isolation (transfer) switch, ALWAYS have power applied to the generator's internal battery charger. This will ensure that the engine will not fail due to a dead battery.
When the generator is set in the
AUTO mode, the generator will
NOTE automically start in the event of comercial power falling below a prescribed level by means of a contact closure that is generated automatically by a transfer switch.