DCA-150SSJU3 — GENERATOR OUTPUTS/ GAUGE READING

DCA-150SSJU3 — GENERATOR OUTPUTS/ GAUGE READING

Maximum Amps

Table 10 shows the maximum amps the generator can pro- vide. DO NOT exceed the maximum amps as listed.

Table 10. Generator Maximum Amps

Model
DCA150SSJU3

 

 

Rated Voltage

Maximum Amps

 

 

Single Phase

33.3 amps (4 wire)

120 Volt

 

 

 

Single Phase

166.7 amps (4 wire)

240 Volt

 

 

 

Three Phase

361 amps

240 Volt

 

 

 

Three Phase

180 amps

480 Volt

 

 

 

Figure 17. AC Voltmeter

Figure 18. AC Voltmeter Gauge

Change-Over Switch

(Volt reading on W-U Lug)

How to Read the Output Terminal Gauge.

The AC ammeter and AC voltmeter change-over switches on the control panel DO NOT effect the generator output. They are provided to help observe how much power is being supplied, produced at the UVWO terminals lugs.

When the voltage change-over board (Figure 16) is jumpered for 3Ø, 240V operation place the AC Voltmeter Change- Over Switch (Figure 17) to the W-U position and the AC Ammeter Change-Over Switch (Figure 19) to the U or W position. Use the AC voltmeter or AC ammeter (Figures 18 and 20) to read the output on the selected leg of the UVWO terminals.

Figure 19. AC Ammeter

Change-Over Switch

NOTE

Figure 20. AC Ammeter (Amp reading on U lug)

The ammeter gauge will only show a reading when the Output Terminal Lugs are connected to a load and in use.

DCA-150SSJU3— OPERATION AND PARTS MANUAL — REV. #0 (11/14/07) — PAGE 45