120VAC GFCI Receptacles

DCA-150SSJU3 — OUTPUT TERMINAL PANEL FAMILIARIZATION

120VAC GFCI Receptacles

There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) recepacles provided on the output terminal panel. These receptacles can be accessed in any voltage selector switch position. Each receptacle is protected by a 20 amp circuit breaker.These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the U, V, and W output terminal lugs.

Pressing the reset button resets the GFCI receptacle after being tripped. Pressing the Test Button (See Figure 10) in the center of the receptacle will check the GFCI function. Both receptacles should be tested at least once a month.

Figure 10. G.F.C.I. Receptacle

Twist Lock Dual Voltage 120/240 VAC Receptacles

There are three 240/139V, 50 amp auxilliary twist-lock (CS-6369) recepacles (Figure 11) provided on the output terminal panel.These receptacles can only be accessed when the voltage change-over board is configured for three- phase 240 operation.

Each auxilliary receptacle is protected by a 50 amp circuit breaker.These breakers are located directly above the GFCI receptacles. Remember the load output (current) on all three receptacles is dependent on the load requirements of the Output Terminal Lugs.

Turn the voltage regulator control knob (Figure 12) on the control panel to obtain the desired voltage.Turning the knob clockwise will increase the voltage, turning the knob counter- clockwise will decrease the voltage.

Figure 12. Voltage Regulator Control Knob

Removing the Plastic Face Plate (HardWire Hookup Panel)

The Output Terminal Lugs are protected by a plastic face plate cover (Figure 13). Un-screw the securing bolts and lift the plastic terminal cover to gain access to the terminal enclosure.

After the load wires have been securely attached to the terminal lugs, reinstall the plastic face plate.

Figure 13. Plastic Face Plate (Output Terminal Lugs)

Figure 11. 240/139V Twist-Lock

Auxiliary Receptacles

DCA-150SSJU3— OPERATION AND PARTS MANUAL — REV. #0 (11/14/07) — PAGE 41

Page 41
Image 41
Multiquip DCA-150SSJU3 120VAC GFCI Receptacles, G.F.C.I. Receptacle, Voltage Regulator Control Knob, 240/139V Twist-Lock