Nordyne SERIES M1B Example of Flat Jack with Flashing, Example of 2½/12 Slant Jack, Slant Deck

Models: AND M5S SERIES M1B

1 40
Download 40 pages 11.4 Kb
Page 12
Image 12
Figure 17. Example of Flat Jack

Figure 17. Example of Flat Jack

with Flashing

Figure 18. Example of 2½/12 Slant Jack

with Flashing

If the home is located in regions where snow accumulation exceeds 7”(HUD snowload zones) use an external roof jack extension (p/n 901937). Extensions are optional accessories and may be purchased through your NORDYNE distributor.

Locating and Cutting Roof & Ceiling Openings

DO NOT ALLOW DEBRIS TO FALL INTO THE FURNACE. THIS COULD CAUSE UNSAFE OPERATION AND VOIDS THE FURNACE WARRANTY. Use the top cap that comes with the furnace packaging (or alternate protector) to prevent debris from falling into the furnace before the fi nal roof jack connection is made

1.Locate center of Roof Jack opening, measure 13 1/2” from the rear wall of closet or alcove along the center line of furnace and fl oor opening. See Figure 19.

2.Cut ceiling and roof holes as follows:

Ceiling = 8 3/4” (222 mm) diameter

Roof = 9 3/8” (238 mm) diameter

Figure 18. Example of 2½/12 Slant Jack IMPORTANT:

R e f e r t o t h e i n s t a l l a t i o n i n s t r u c t i o n s p r o v i d e d w i t h o p t i o n a l a i r c o n d i t i o n i n g p a c k a g e s w h e n i n s t a l l i n g furnaces with optional cooling c o i l c a b i n e t o r w i t h o p t i o n a l C * s e r i e s i n d o o r c o i l s .

 

 

20"

 

 

 

C

 

 

 

L

 

 

 

10"

 

 

REAR WALL OF CLOSET OR ALCOVE

 

24"

OUTLINE

 

13 1/2"

FURNACE

CEILING

 

 

CUT-OUT FOR

C

 

 

 

FLUE AND

L

 

 

 

ROOF JACK

 

 

 

 

FURNACE

 

 

 

OUTER

 

 

 

DOOR

Figure 19. Cut-Out Dimensions for

Flue & Roof Jack

ROOF JACK SERIES

IF ROOF PITCH IS:

SLANT DECK

“X” FACTOR

FLASHING NUMBER

IS:

 

 

 

 

 

 

 

2” in 12”

903893 (2.5/12)

2-1/8”

 

2-1/2” in 12”

903893 (2.5/12)

2-1/2”

“F Series

3” in 12”

903894 (3/12)

2-7/8”

 

3-1/2” in 12”

903894 (3/12)

3-1/4”

 

4” in 12”

903895 (4/12)

3-5/8”

 

4-1/2” in 12”

903895 (2.5/12)

2-1/8”

“S” Series (2.5 / 12

5” in 12”

903895 (2.5/12)

2-1/2”

5-1/2” in 12”

903894 (3/12)

2-7/8”

Pitch only)

6” in 12”

903894 (3/12)

3-1/4”

 

 

6-1/2” in 12”

903895 (4/12)

3-5/8”

Optional Deck Flashings for Flat and 2.5/12 Pitch Roof Jacks. 4/12 Pitch Roof Jacks not applicable.

Table 5. Slant Deck Flashings

12

Page 12
Image 12
Nordyne SERIES M1B Example of Flat Jack with Flashing, Example of 2½/12 Slant Jack, Cut-OutDimensions for Flue & Roof Jack