Control Module Status Indicators - M1M Series

Red LED Indicator

Status

 

 

Steady ON

Control OK

 

 

Steady OFF

No power

 

 

Rapid fl ash

False fl ame or internal control fault

 

 

One fl ash

Limit switch is open

 

 

Two fl ashes

Pressure switch is open

 

 

Three fl ashes

Pressure switch is stuck closed

 

 

Four fl ashes

Lockout due to failed ignition

 

 

Five fl ashes

L1 neutral reversed or L1 voltage not present on L1

 

 

Flame Status - A Yellow LED labeled “Flame” is provided to indicate fl ame status. When fl ame is sensed, the fl ame LED is lit. If fl ame sense is weak, yellow LED will fl ash.

 

Control Module Status Indicator - M1B

 

 

Red LED Indicator

Status

 

 

One fl ash

The control is in lock-out because the inducer centrifugal switch is or

was stuck closed.

 

 

 

Two fl ashes

The control is in lockout because the signal was not received by the

control that the inducer centrifugal switch had closed within the time.

 

 

 

 

The control is in lockout because a failed ignition attempt, a gas valve

Three fl ashes

error, or a false fl ame sensed during the warm up period. If false fl ame

has been sensed, the control will return to normal operation, and repeat

 

 

ignition sequence when the false fl ame is not present.

 

 

Four fl ashes

The control is in lockout due to a failure within the control board

 

 

Control Module Status Indicator - M5S Series

The LED indicator(s) on the oil primary control provides lockout, recycle and cad cell indications.

Honeywell R7184 Control

Green LED Indicator

Status

 

 

On

Cad cell is sensing flame (could be fl ame or stray light)

 

 

Off

Cad cell is not sensing flame

 

 

Flashing - 1/2 sec. on, 1/2 sec. off

Lockout/Restricted Lockout

 

 

Flashing - 2 sec. on, 2 sec. off

Recycle

 

 

Beckett 7505 Control

LED Indicator Color

On Continuously

Flashing

 

 

 

Red

Restricted (hard) lockout

Soft lockout

 

 

 

Green

Cad cell is sensing fl ame -

Recycle

(could be fl ame or stray light)

 

 

 

 

 

Yellow

Pump prime mode or reset

N/A

button currently held for 15+ sec.

 

 

 

Table 9. Control Module Status Indicators