Nordyne SERIES M1B, AND M5S Optional Accessories, Coil Cavity Damper, Damper without Coil Cavity

Models: AND M5S SERIES M1B

1 40
Download 40 pages 11.4 Kb
Page 28
Image 28
OPTIONAL ACCESSORIES

the cad cell is operational, replace the primary control.

4.If the LED continues to fl ash at the interval listed above, verify that the control is not in restricted mode. If in restricted mode, reset it. If not in restricted mode, replace the control.

5.If the (LED indicator for R7184 control; green LED for 7505 control) stays off while the fl ame is on, check the cad cell sighting for view of the fl ame.

6.If the burner locks out, check the cad cell resistance. (See Table 8)

7.If the burner stays running, the system is operational.

8.If the (LED indicator for R7184 control; green

LED for 7505 control) is off, check the cad cell assembly after disconnecting the line voltage.

Burner will not start and the LED indicator is

ashing at 2 seconds on, 2 seconds off for R7184 (or the green LED is fl ashing for 7505).

Hold the reset button down for 1 - 2 seconds. If LED indicator continues to fl ash, wait for 60 - 70 seconds. If it still continues to fl ash, replace the primary control.

Honeywell R7184 control: To check cad cell resistance, press and release the button during the run mode, with the igniter off.The LED will

ash to indicate the cad cell resistance. For proper burner operation, it is important that the cad cell resistance is under 1600 Ohms. For cad cell resistance, see Table 8.

Beckett 7505 control: To check cad cell resistance, unplug the cad cell leads (yellow wires) from the control.Measure the resistance with a meter in the conventional way (when a

ame is present).For proper burner operation, it is important that the cad cell resistance is under 1,600 Ohms.

OPTIONAL ACCESSORIES

Necessary when the Furnace is Used with Some Central Air Conditioners

If an air conditioner is installed that does not use the furnace blower for air distribution and operates independently of the furnace, the thermostat system must have an interlock to prevent the furnace and air conditioner from operating at the same time. This interlock system usually contains either a “Heat-Cool” switch which must be turned to one of the positions to activate heat or cool operation, or a positive “OFF” switch on the cooling thermostat.

The furnace must also be equipped with an automatic damper to prevent cold air from being discharged up around the heat exchanger (NORDYNE p/n 901996 for furnaces without coil cavity, or p/n 901083 with coil cavity). See Figure 36 or 37.Cold air may cause condensation inside the heat exchanger which can rust and lead to early failure.

Figure 36. Coil Cavity Damper

LED Flashes (Ohms)

Cad Cell Resistance

 

 

1

0-400

2

400-800

3

800-1600

4

>1600

Table 8. Cad Cell Resistance when

sensing flame

Figure 37. Damper without Coil Cavity

28

Page 28
Image 28
Nordyne SERIES M1B, AND M5S Optional Accessories, Coil Cavity Damper, Cad Cell Resistance when sensing flame