42Chapter 5 Connecting the server to power

Figure 13

Example setup of 600r with peripherals

To connect the 600r server to power

WARNING

Risk of personal injury and risk of hardware failure

You must connect the power outlets that are used by the CallPilot server and its peripheral devices to the same single-point ground reference as the one used by the switch with MGate cards connected to the CallPilot server.

If this requirement is not met, power transients can cause personal injury, hardware failure, or both. For more information about single-point grounding requirements, seeInstallation and Configuration Task List (NN44200-306).

Nortel CallPilot

600r Server Hardware Installation

NN44200-307 01.03 Standard

5.014 May 2008

Copyright © 2007-2008, Nortel Networks

Page 42
Image 42
Nortel Networks manual To connect the 600r server to power, Example setup of 600r with peripherals