October 2006 | Installing the server and connecting the peripheral devices |
Connecting the server to power
Before you begin
Ensure that proper power and grounding are available for all the power outlets serving the CallPilot server and its associated peripherals. Power for these devices must be wired and fused independently of all other receptacles and referenced to the same ground as the PBX system.
Aqualified electrician must implement the single-point ground reference as required among the power outlets of the CallPilot server, its associated peripherals, and the power outlets of the switch.
Provide a sufficient number of properly grounded power outlets or power bars for all equipment.
The single-point ground (SPG) required by the system can be an isolated ground (IG) bus or AC equipment ground (ACEG) bus in the service panel or transformer. The system must be connected to safety ground/protective earth in accordance with NEC requirements. For international use, the system must be connected to safety ground/protective earth in accordance with Paragraph 2.5 of EN60950/IEC950.
Note: Refer to Large System: Planning and Engineering (553-3021-120) for a complete description of approved ground sources and methods. Insulated ground wire must be used for system grounding.
703t Server Hardware Installation | 63 |