Page204 of 544 Powersupplies
553-3011-100 Standard14.00 January 2002
Uninterrupted Power Supply (UPS)
A 750VA Uninterrupted Power Supply (UPS) may be connected to AC-
powered systems in order to provide a continuous supply of AC-power.
If two cabinets are equipped, two 750VA UPSs or one 1.5KVA UPS can be
used.

Battery charging in AC-powered systems

During normal operation, the AC/DC power supply (NTAK04 or NTDK78)
provides a constant float voltage to the reserve batteries. This charger voltage
is not adjustable and will not provide equalization voltages. See Table65.

Reserve time

Table66 outlines the Ampere hours required (AHR) per cabinet during a
power failure. The reserve times are based on nominal load for a typical
installation.
Features of the Option 11C M ini power supply
This section describes the Option 11C NTDK15 Mini AC power supply.
Table 6 5
NTAK04 or NTDK78 AC/DC power interface to reserve power systems
Minimum Nominal Maximum
Float Voltage 52.95 Volts 53.6 Volts 54.50 Volts
Charge Currenta
a. The charge current available to the reser ve batteries depend s on the system co nfiguration and the line size.
1.0 Amps 7.0 Amps
Table 6 6
Reserve time
Duration of Power Failure AHRs required per Option 11C cabinet
30 40 minutes 6 AHR
1.5 2 hours 12 AHR
3 4 hours 25 AHR