Omega WI8XX-U manual Display Color Examples continued, Amber

Models: WI8XX-U

1 92
Download 92 pages 14.59 Kb
Page 53
Image 53
4.3.7.5.1Display Color Examples (continued)

4.3.7.5.1Display Color Examples (continued)

Example 3:

Output 1 = Relay, Setpoint 1 = 300, Output 2 = Relay, Setpoint 2 = 200

Alarm 1 & 2 Setup: Deviation, Band, "ALR.H" = 10

Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red

Display Colors change sequences:

 

 

AMBER

 

AMBER

 

 

 

AMBER

 

 

 

 

 

RED

 

 

AMBER

 

---------------

------

 

•------

•--------------------------------

 

 

 

 

 

 

 

•------

•-------

•----------------

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

190

 

200

210

 

 

 

 

 

 

290

300

310

 

 

 

 

 

 

 

 

Alarm 1 is designed to monitor the Input Value around the Setpoint 1.

 

 

 

 

Alarm 2 is designed to monitor the Input Value around the Setpoint 2.

 

 

 

 

 

Example 4:

 

 

 

= Relay, Setpoint 1 = 200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output 2

= Relay, Setpoint 2 = 200

 

" = 20

 

 

 

 

 

 

 

 

 

 

Alarm 1 Setup: Deviation, Band, "

ALR.H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: "

 

" =

 

 

" = 10, "

 

" = 5

 

 

 

 

 

Alarm 2 Setup: Deviation, Hi/Low, "

ALR.H

LR.L

 

 

Display colors change

 

 

 

 

N.CLR

 

Green, "

1.CLR

" =

Amber,

"

2.CLR

" = Red

 

 

 

Color Display Setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sequences:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

---------------•--AMBER

 

----------------RED

 

------------- --------------GREEN

-------------• RED

---------------------•

 

AMBER

0

 

 

180

 

 

195

200

 

210

 

 

220

 

 

 

 

 

47

Page 53
Image 53
Omega WI8XX-U manual Display Color Examples continued, Amber