Omega WI8XX-U manual Part, Specifications, ON/OFF CONTROL OUTPUT 1, ALARM 1 & 2 PROGRAMMABLE

Models: WI8XX-U

1 92
Download 92 pages 14.59 Kb
Page 77
Image 77
INSULATION Power to Output:
Power to Relays/SSR Outputs: Relays/SSR to Relay/SSR Outputs:
GENERAL Display:
Digital Filter:

PART 6

 

SPECIFICATIONS

 

ON/OFF CONTROL OUTPUT 1 & 2

Relay:

250 Vac or 30 Vdc @ 3 A (Resistive Load), SPDT

Solid State Relay (SSR):

20 to 265 Vac @ 0.05 to 0.5 A (Resistive Load);

DC Pulse:

continuous

Non-Isolated; 10 Vdc @ 20 mA

Analog Output (Output 1 only)

Non-Isolated, 0 to 10 Vdc or 0 to 20 mA, 500 Ω

Operation:

max

Direct (cool), reverse (heat); deadband; single

Configuration

sensing input

Output 1 and 2 can be configured as Alarm 1

 

and 2, respectively. Analog Output for Output 1

 

can be configured as retransmission.

ALARM 1 & 2 (PROGRAMMABLE)

Type:

SPDT Relay, SSR, and DC Pulse

Operation:

High/low, above/below, band, latch/unlatch,

 

normally open/normally closed and

 

process/deviation; front panel configurations;

 

single/multiple sensing input(s)

ANALOG RETRANSMISSION OUTPUT (PROGRAMMABLE)

Type:

Non-Isolated, Retransmission 0 to 10 Vdc or

Operation:

0 to 20 mA, 500 Ω max (Output 1 only).

Single sensing input; accuracy is + 1% of FS

 

when following conditions are satisfied:

1) Input is not scaled below 1% of Input FS.

2) Analog Output is not scaled below 3% of Output FS.

2300 Vac per 1 min. test

1500 Vac per 1 min. test

(Low Voltage/Power Option)

2300 Vac per 1 min. test

2300 Vac per 1 min. test

4-digit, 9-segment LED, 10.2mm (0.40") and 21mm (0.83") red, green and amber programmable colors

Programmable

71

Page 77
Image 77
Omega WI8XX-U manual Part, Specifications, ON/OFF CONTROL OUTPUT 1, ALARM 1 & 2 PROGRAMMABLE