C H A P T E R 3
INSTALLATION
The following sections describe UPS storage requirements and the installation and startup of the UPS.
Unpacking and Inspection
Carefully unpack the UPS and any other cabinets, making sure to retain the packaging materials. Examine each unit carefully for any signs of damage and immediately notify your distributor if damage is present.
UPS and Battery Cabinet Storage
If you plan to store the UPS or battery cabinets prior to use, store them in a cool, dry environment. Storage temperature should not exceed
35°C (95°F) in order to preserve battery life. For longer term storage, energize the power processing unit and battery cabinet for approximately 8 hours every 90 days in order to maintain battery charge.
Whenever the units are not energized, verify the circuit breaker on all battery cabinets is returned to the OFF (O) position (see Figure 4 on page 26).
Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.com | 23 |