Installation
12. Press and hold the Output On button until you hear the UPS beep (approximately one second).
The µindicator remains lit and the Self Test indicator turns on. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. See “Normal Mode” on page 50 for more information.
13.If you connected a REPO switch to the UPS, test the switch while the UPS is operating to ensure proper operation.
Press the REPO switch. The UPS shuts down and stops providing power to the equipment. To restart the UPS, follow the startup procedure beginning on page 47.
NOTE If the REPO test fails and the UPS does not shutdown, contact your service representative.
Troubleshooting Tips
If you should encounter any problems during startup, see the troubleshooting chart on page 75.
The battery cabinets are shipped with the batteries charged. However, batteries may lose some of the charge during shipping and storage. You can use the UPS immediately after unpacking, but it may not provide the