Installation
|
| Mounting Holes |
| |
|
|
| Plug/Receptacle | |
|
|
| PPU Connector | |
| Access Hole |
|
|
|
| for Conduit |
|
|
|
|
|
| Three Foot Cord |
|
|
| Terminal Block |
|
|
| Figure 6. Optional REPO Cord Junction Box |
| ||
|
| Optional REPO Cord Junction Box Connections |
| |
Wire Function | Terminal | Terminal Wire Size | Suggested Wire | |
|
| Position | Rating | Size |
REPO | L1 |
|
| |
| L2 | 12 - 22 AWG | 18 AWG (0.75 mm2) | |
| (4 - 0 mm2) | |||
| Ground |
| ||
|
|
|
NOTE The REPO function activates when L1 and L2 are shorted together.
UPS Hardwired InstallationW A R N I N G
Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation.
Use the following procedure to install the PPU and battery cabinets:
1.Place the UPS near the equipment to be protected. The UPS should be well ventilated and away from direct sunlight or other heat source.
Place the PPU underneath or beside the battery cabinets as shown in Figure 7.
NOTE Do not connect more than six standard battery cabinets to the PPU. For extended battery run times, contact your local distributor for additional battery cabinets. Do not place more than six cabinets in one stack (the PPU is equal to two cabinets).
Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.com | 29 |