Installation

 

 

Mounting Holes

 

 

 

 

Plug/Receptacle

 

 

 

PPU Connector

 

Access Hole

 

 

 

 

for Conduit

 

 

 

 

 

 

Three Foot Cord

 

 

 

Terminal Block

 

 

 

Figure 6. Optional REPO Cord Junction Box

 

 

 

Optional REPO Cord Junction Box Connections

 

Wire Function

Terminal

Terminal Wire Size

Suggested Wire

 

 

Position

Rating

Size

REPO

L1

TB1-4

 

 

 

L2

TB1-5

12 - 22 AWG

18 AWG (0.75 mm2)

 

(4 - 0 mm2)

 

Ground

TB1-6

 

 

 

 

NOTE The REPO function activates when L1 and L2 are shorted together.

UPS Hardwired Installation

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation.

Use the following procedure to install the PPU and battery cabinets:

1.Place the UPS near the equipment to be protected. The UPS should be well ventilated and away from direct sunlight or other heat source.

Place the PPU underneath or beside the battery cabinets as shown in Figure 7.

NOTE Do not connect more than six standard battery cabinets to the PPU. For extended battery run times, contact your local distributor for additional battery cabinets. Do not place more than six cabinets in one stack (the PPU is equal to two cabinets).

Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.com