C H A P T E R 7

TROUBLESHOOTING

The Prestige UPS is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Use the following troubleshooting chart to determine the UPS alarm condition.

Indicator Legend

Unlit

Amber

Green

Flashing

Condition

Possible Cause

Action

 

UPS does not turn on.

UPS is not connected correctly to

Check connections to the power source.

 

the power source.

 

 

 

 

 

 

UPS input breaker is off.

Reduce load, then reset breaker.

 

 

 

Load does not turn on.

UPS has not been activated.

Press the Output On button for one

 

 

second, then release.

 

 

 

UPS beeps occasionally.

Normal operation.

None. UPS is protecting your

 

 

equipment.

 

 

 

indicator remains

Utility line is out of specification.

Test wall socket, repair as required.

lit, even though line

 

 

 

UPS input breaker is tripped.

Reduce load, then reset breaker.

voltage is present.

 

 

 

UPS does not provide

Battery circuit breakers are in the

Switch the battery circuit breaker to the

the expected backup time.

OFF (O) position.

ON ( ) position for all connected

 

 

battery cabinets.

 

 

 

 

Low battery capacity.

Allow battery to charge for 24 hours,

 

 

then retest.

 

 

 

 

Protected equipment power

Reduce load, then retest.

 

requirements exceed UPS capacity.

 

 

 

 

 

Communications do not

Incorrect communications cabling.

Verify cable integrity (see page 66).

function properly.

 

 

 

Incorrect baud rate.

Select a new baud rate (see page 65).

 

 

 

 

 

Incorrect communication mode.

Select a new communication mode (see

 

 

Chapter 5).

 

 

 

 