Specifications

Electrical Specifications for the Prestige 6000 with PPDM

Use the following tables to determine load wiring requirements when the PPDM is used with the UPS. The distribution of your load on the available outputs of the PPDM may affect the maximum load obtainable.

Prestige 6000 PPDM Ratings with a Model 6000 UPS

PPDM Model

Input Utility Voltage

Input

Output Voltage and

Maximum Output

 

 

and Selected UPS

Current

Maximum Current

Apparent Power**

 

 

Output Voltage

 

 

 

 

208:120/208 Hardwired

220 Vac

24A

127/220 Vac (60 Hz only),

5500 VA

 

(60 Hz only)

 

30.0/25.0A

 

 

 

 

 

 

 

208:120/208 Hardwired

208 Vac

24A

120/208 Vac,

5200 VA

 

 

 

30.0/25.0A

 

 

 

 

 

 

 

208:120 L5-30R

208 Vac

24A

120 Vac,

5200 VA

 

 

 

43.3A*

 

 

 

 

 

 

 

208:120/208 L6-20R

208 Vac

24A

120/208 Vac,

5200 VA

 

 

 

15.0/20.0A

 

 

 

 

 

 

 

208:120/208 L6-30R

208 Vac

24A

120/208 Vac,

5200 VA

 

 

 

15.0/25.0A

 

 

 

 

 

 

 

208:120/240 L14-30R

208 Vac

24A

120/240 Vac,

5000 VA

 

 

 

15.0/21.1A

 

 

 

 

 

 

 

240:120/240 Hardwired

200 - 240 Vac

25A

100 - 120/200 - 240 Vac,

6000 VA

 

 

 

30.0/25.0A

 

 

 

 

 

 

 

240:120/240E Hardwired

200 - 240 Vac

24A

100 - 120/200 - 240 Vac,

6000 VA

 

 

 

30.0/25.0A

 

 

 

 

 

European IT Neutral

 

 

 

 

 

 

 

240:120 L5-30R

200 - 240 Vac

24A

100 - 120 Vac,

5800 VA

 

 

 

48.3A*

 

 

 

 

 

 

 

240:120/240 L6-20R

200 - 240 Vac

24A

100 - 120/200 - 240 Vac,

5800 VA

 

 

 

15.0/20.0A

 

 

 

 

 

 

 

240:120/240 L6-30R

200 - 240 Vac

24A

100 - 120/200 - 240 Vac,

5800 VA

 

 

 

15.0/24.7A

 

 

 

 

 

 

 

240:120/240 L14-30R

200 - 240 Vac

24A

100 - 120/200 - 240 Vac,

5800 VA

 

 

 

15.0/24.7A

 

 

 

 

 

 

 

 

*Total of currents in all available 100 - 120V output connections.

**Ratings based on 4000W load on PPDM, plus sufficient linear inductive load to achieve the current rating of the input plug, not to exceed VA rating of PPU.

NOTE Input and output currents are approximately the same when load is powered through bypass.

72