Specifications
Electrical Specifications for the Prestige 6000 with PPDM
Use the following tables to determine load wiring requirements when the PPDM is used with the UPS. The distribution of your load on the available outputs of the PPDM may affect the maximum load obtainable.
Prestige 6000 PPDM Ratings with a Model 6000 UPS
PPDM Model | Input Utility Voltage | Input | Output Voltage and | Maximum Output |
|
| and Selected UPS | Current | Maximum Current | Apparent Power** |
|
| Output Voltage |
|
|
|
|
208:120/208 Hardwired | 220 Vac | 24A | 127/220 Vac (60 Hz only), | 5500 VA | |
| (60 Hz only) |
| 30.0/25.0A |
|
|
|
|
|
|
| |
208:120/208 Hardwired | 208 Vac | 24A | 120/208 Vac, | 5200 VA | |
|
|
| 30.0/25.0A |
|
|
|
|
|
|
| |
208:120 | 208 Vac | 24A | 120 Vac, | 5200 VA | |
|
|
| 43.3A* |
|
|
|
|
|
|
| |
208:120/208 | 208 Vac | 24A | 120/208 Vac, | 5200 VA | |
|
|
| 15.0/20.0A |
|
|
|
|
|
|
| |
208:120/208 | 208 Vac | 24A | 120/208 Vac, | 5200 VA | |
|
|
| 15.0/25.0A |
|
|
|
|
|
|
| |
208:120/240 | 208 Vac | 24A | 120/240 Vac, | 5000 VA | |
|
|
| 15.0/21.1A |
|
|
|
|
|
|
| |
240:120/240 Hardwired | 200 - 240 Vac | 25A | 100 - 120/200 - 240 Vac, | 6000 VA | |
|
|
| 30.0/25.0A |
|
|
|
|
|
|
| |
240:120/240E Hardwired | 200 - 240 Vac | 24A | 100 - 120/200 - 240 Vac, | 6000 VA | |
|
|
| 30.0/25.0A |
|
|
|
|
| European IT Neutral |
|
|
|
|
|
|
| |
240:120 | 200 - 240 Vac | 24A | 100 - 120 Vac, | 5800 VA | |
|
|
| 48.3A* |
|
|
|
|
|
|
| |
240:120/240 | 200 - 240 Vac | 24A | 100 - 120/200 - 240 Vac, | 5800 VA | |
|
|
| 15.0/20.0A |
|
|
|
|
|
|
| |
240:120/240 | 200 - 240 Vac | 24A | 100 - 120/200 - 240 Vac, | 5800 VA | |
|
|
| 15.0/24.7A |
|
|
|
|
|
|
| |
240:120/240 | 200 - 240 Vac | 24A | 100 - 120/200 - 240 Vac, | 5800 VA | |
|
|
| 15.0/24.7A |
|
|
|
|
|
|
|
|
*Total of currents in all available 100 - 120V output connections.
**Ratings based on 4000W load on PPDM, plus sufficient linear inductive load to achieve the current rating of the input plug, not to exceed VA rating of PPU.
NOTE Input and output currents are approximately the same when load is powered through bypass.
72 | Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.com |