Communication
| SELECT LAN CONFIGURATION | |
1 | > | NOVELL |
2 | > | AS400 |
3 | > | |
4 | > | CUSTOM CONFIGURATION |
Q | > | TO QUIT THIS MENU |
ENTER SELECTION >+>
Select the AS400 option if you are using OnliSafe software to monitor the UPS.
The Custom Configuration option has two screens: the first screen has options available for inverter shutdown, and the second screen has options available for the contact configuration. Consult your shutdown software documentation for details on the required signal states for configuring LAN communications.
SELECT CUSTOM LAN CONFIGURATION
Instructions: Choose the desired inverter shutdown function.
Warning: It is recommended that this feature should not be used with normal
A> Inverter shutdown control is enabled active HIGH (+12V) B > Inverter shutdown control is enabled active LOW
Q > TO QUIT THIS MENU
ENTER SELECTION >=>
SELECT CUSTOM LAN CONFIGURATION
Instructions: Choose the desired contact configuration.
1> UTIL_FAIL is active closed, LOW_BATT is active closed
2 > UTIL_FAIL is active open, LOW_BATT is active closed 3 > UTIL_FAIL is active closed, LOW_BATT is active open 4 > UTIL_FAIL is active open, LOW_BATT is active open
Q > TO QUIT THIS MENU
ENTER SELECTION >=>