Installation

4.Select the correct UPS output voltage according to the PPDM model:

PPDM Model Number

UPS Voltage Selector Switch Position*

 

208: 120/208 Hardwired

Set to 208V for 120/208V PPDM output

 

Set to 220V for 127/220V PPDM output (60-Hz units only)

 

 

 

208: 120 L5-30R

208

 

 

 

 

208: 120/208 L6-20R

208

 

 

 

 

208: 120/208 L6-30R

208

 

 

 

 

208: 120/240 L14-30R

208

 

 

 

 

240:120/240 Hardwired

240:120/240 L5-30R

 

Set to 200V for 100/200V PPDM output

240: 120/240 L6-20R

Set to 220V for 110/220V PPDM output

 

240: 120/240 L6-30R

Set to 230V for 115/230V PPDM output

 

Set to 240V for 120/240V PPDM output

 

240:120/240 L14-30R

240:120/240E Hardwired

*The UPS output voltage should match local voltages.

Using a screwdriver, turn the switch to the corresponding position of the output voltage required (see Figure 15). The output voltage is factory-set to 220V.

C A U T I O N

Do not turn the Voltage Selector switch while the UPS is operating (see “Changing the Output Voltage” on page 53). Changing the output voltage while the UPS is operating may cause an emergency power-off.

Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.com

41