Communication

Communications Mode Reference Chart

The following chart defines the UPS serial port contacts. Serial communication is not available with 3Com and AS/400 network configurations. Use only the applicable pins for the selected communication mode; otherwise, interference problems may occur.

Communication Mode

Function

Signal Name

Pin No.

True Condition

 

Serial

Data to UPS

RS232 TxD

2

N/A

 

 

 

 

 

 

Data from UPS

RS232 RxD

3

N/A

 

 

 

 

 

 

 

Signal Ground

 

7

 

 

 

 

 

 

 

Novell

Battery On

ON.AC

14/16

Open

(Default)

 

 

 

 

 

Low Battery

TWO.MIN

23/24

Closed

 

 

 

 

 

 

 

 

Signal Ground

 

7/15/25

 

 

 

 

 

 

 

Novell

Battery On

ON.AC

14/16

Closed

(Custom)

 

 

 

 

 

Low Battery

TWO.MIN

23/24

Closed

 

 

 

 

 

 

 

 

Signal Ground

 

7/15/25

 

 

 

 

 

 

 

3Com

Shutdown (Remote)

SHUT.DOWN

2

Positive Voltage

(Default)

 

 

 

 

 

Low Battery

LOW.BATT

9

Positive Voltage

 

 

 

 

 

 

 

Battery On

PWR.FAIL

10

Positive Voltage

 

 

 

 

 

 

 

Signal Ground

 

7

 

 

 

 

 

 

 

AS/400

UPS Available

UPS Available

11/13

Closed

 

 

 

 

 

 

Battery On

Utility Failure

14/16

Closed

 

 

 

 

 

 

Bypass

UPS Offline

17/19

Closed

 

 

 

 

 

 

Low Battery

Low Battery

23/24

Closed

 

 

 

 

 

 

 

Signal Ground

 

12/15/18/25

 

 

 

 

 

 

 

 

NOTE Pin numbers separated by a forward slash ( / ) are connected together internally.

Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.com

67