Specifications

Model 4500 UPS (Nominal Operating Specifications)

Output VA

Output

Output

Input Current

Output Current

Normal

On Battery

 

 

Voltage

Watts

 

 

(BTUs/hr)

(BTUs/hr)

 

3750

200

2500

14.6A

19.0A

< 1200

< 1600

 

 

 

 

 

 

 

 

 

3900

208

2600

14.6A

19.0A

< 1200

< 1700

 

 

 

 

 

 

 

 

 

4125

220

2750

14.6A

19.0A

< 1300

< 1800

 

 

 

 

 

 

 

 

 

4300

230

2900

14.6A

19.0A

< 1400

< 1900

 

 

 

 

 

 

 

 

 

4500

240

3000

14.6A

19.0A

< 1400

< 1900

 

 

 

 

 

 

 

 

 

Model 4500 with PPDM (Nominal Operating Specifications)

Output VA

Output Voltage

Output Watts

Normal (BTUs/hr)

On Battery

 

(PPU)

(PPU)

 

 

(BTUs/hr)

 

3750

200

2275

< 1900

< 2400

 

 

 

 

 

 

 

3900

208

2375

< 2000

< 2400

 

 

 

 

 

 

 

4125

220

2525

< 2000

< 2500

 

 

 

 

 

 

 

4300

230

2675

< 2100

< 2600

 

 

 

 

 

 

 

4500

240

2775

< 2200

< 2700

 

 

 

 

 

 

 

Physical Specifications

Parameter

PPU

Battery Cabinet

PPDM

 

Height

283 mm (11.13 in)

142.5 mm (5.61 in)

283 mm (11.13 in)

 

 

 

 

Width

252 mm (9.91 in)

252 mm (9.91 in)

252 mm (9.91 in)

 

 

 

 

Depth

Plug/Receptacle: 406 mm (16 in)

400 mm (15.75 in)

Plug/Receptacle: 406 mm (16 in)

 

Hardwired: 463 mm (18.25 in)

 

Hardwired: 463 mm (18.25 in)

 

 

 

 

Weight

18 kg (39 lb)

23.6 kg (52 lb)

37 kg (82 lb)

 

 

 

 

 

70

Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.com