UPS SETUP

Floor Loading

When planning the installation, consider the UPS weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings. The approximate weights are shown in the following table.

Standard Model Floor Loadings (2-High/3-High Cabinets)

Powerware 9155

Maximum

Point Loading

Distributed

 

Weight (lb)

(lb/in2)

Loading (lb/ft2)

 

 

 

2-High UPS

352

88

166

 

 

 

 

 

 

3-High UPS

590

148

278

 

 

 

 

 

 

3-High UPS with

558

140

263

 

Isolation

 

 

 

 

Transformer

 

 

 

 

 

 

 

 

 

2-High EBM

480

120

226

 

 

 

 

 

 

3-High EBM

710

178

335

 

 

 

 

 

 

Clearances

The following clearances are recommended for the Powerware 9155

UPS:

From Front of Cabinet

36” (91.4 cm) working space

From Back of Cabinet

6” (15.2 cm)

 

 

8

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com