UPS SETUP
Floor LoadingWhen planning the installation, consider the UPS weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings. The approximate weights are shown in the following table.
Standard Model Floor Loadings
Powerware 9155 | Maximum | Point Loading | Distributed |
|
Weight (lb) | (lb/in2) | Loading (lb/ft2) |
| |
|
| |||
352 | 88 | 166 |
| |
|
|
|
|
|
590 | 148 | 278 |
| |
|
|
|
|
|
558 | 140 | 263 |
| |
Isolation |
|
|
|
|
Transformer |
|
|
|
|
|
|
|
|
|
480 | 120 | 226 |
| |
|
|
|
|
|
710 | 178 | 335 |
| |
|
|
|
|
|
The following clearances are recommended for the Powerware 9155
UPS:
From Front of Cabinet | 36” (91.4 cm) working space |
From Back of Cabinet | 6” (15.2 cm) |
|
|