OPERATION

17.Select the System On option; press the button.

18.Confirm the selection. Press and hold the button for three seconds, until the UPS stops beeping.

The UPS goes to Bypass mode for five seconds, and then the indicator illuminates. Each UPS should be in Normal mode.

19.Press the ESC button until the Eaton Powerware logo appears.

20.Auto-calibrate the load (with 10% minimum load recommended):

S Using the button, scroll to the Settings menu and then press the button twice to select the User Settings menu.

SUsing the button, scroll to the Parallel Operation Settings option and press the button.

SUsing the button, scroll to the Start Auto Calibration option and

press the button to select the option. Press and hold the button for a second to begin the process.

21.After calibration completes (in less than a minute), verify the load sharing through the front panel:

S Using the button, scroll to the Measurements menu and press the button twice to select the Parallel System menu.

S Select and view the voltage meter options.

22.Press the ESC button until the Eaton Powerware logo appears.