OPERATION

Restarting the Parallel System

To restart the parallel system:

1.Verify that all UPS breakers on the parallel tie cabinet are in the OFF position.

2.Switch on utility power where the UPSs are connected.

3.Wait for the front panel LCD to illuminate. The indicator flashes on each UPS.

4.Switch all battery circuit breakers to the ON position. The indicator stops flashing on each UPS.

5.Switch the UPS breakers on the parallel tie cabinet to the ON position.

6.Verify that no alarms appear on the UPS front panel display.

If the indicator is flashing, do not proceed until all alarms are clear. Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.

7.Press the ESC button once and then press the button to select the TURN UPS ON/OFF menu.

8.Press the button to select the System On option; press the

button.

9.Confirm the selection. Press and hold the button for three seconds, until the UPS stops beeping.

The UPS goes to Bypass mode for five seconds, and then the indicator illuminates. Each UPS should be in Normal mode.

10.Press the ESC button until the Eaton Powerware logo appears.

52