OPERATION
Configuring the UPS for EBMsNOTE Each UPS in a parallel system must have its own EBM and the same number of
EBMs to ensure consistent runtimes.
To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:
1.Press any button on the front panel display to activate the menu options.
2. Using the button, scroll to the Settings menu.
3.Press the button twice to select the User Settings menu.
4.Using the button, scroll to the Number of Battery Strings option and press the button.
5. Use the or buttons to select the number of strings according to your UPS configuration:
All | Number of Strings |
|
|
|
|
UPS + 1 EBM | 6 |
|
|
|
|
UPS + 2 EBMs | 10 |
|
|
|
|
UPS + 3 EBMs | 14 |
|
|
|
|
UPS + 4 EBMs | 18 |
|
|
| |
All | Number of Strings |
|
|
|
|
UPS + 1 EBM | 10 |
|
|
|
|
UPS + 2 EBMs | 16 |
|
|
|
|
UPS + 3 EBMs | 22 |
|
|
|
|
6.Press the button to save the setting.
7.Press the ESC button until the Eaton Powerware logo appears.
EATON Powerware® 9155 Parallel UPS | 49 |